RWB 6104 WMNX Page 1Potential for Fire, Smoke and Asphyxiation HazardsTo the Homeowner or Equipment Owner:Please read and carefully follow all ins
Page 10 RWB 6104 WMNX Fuel supply below the level of the burner – When the fuel supply is more than eight feet below the level of the burner, a two-
RWB 6104 WMNX Page 117. RECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner, enters a 60 second recycle d
Page 12 RWB 6104 WMNX Start the Burner and Set Combus-tionStart-up and Initial Settings Open the shutoff valves in the oil supply line to the burner.
RWB 6104 WMNX Page 13Set Combustion using Test Instruments Set the stack or over-fi re draft to the level speci-fi ed by the appliance manufacturer.
Page 14 RWB 6104 WMNX Cover InstallationInstall the four cover mounting thumb screws in the cover mounting plate. Install the cover over the mounting
RWB 6104 WMNX Page 15Loosen the two screws securing the rear door. Swing the door to the right and down.Loosen the splined nut.Remove the nozzle
Page 16 RWB 6104 WMNX 5/32” GAP1/4” above nozzle center3/32” Nozzle-to-tip SpacingSK9664Nozzle fl ow rate U. S. gallons per hour of No. 2 fuel oil whe
RWB 6104 WMNX Page 17The rear door must be kept tightly closed. The adjustment screw may now be turned to adjust the head/air setting. Turn the a
Page 18 RWB 6104 WMNX Replacement Parts Diagram
RWB 6104 WMNX Page 19For best performance specify genuine Beckett replacement partsReplacement Parts ListItem Description Part No.1 Head/Air adju
Page 2 RWB 6104 WMNX
Page 20 RWB 6104 WMNX LimitedWARRANTYFor Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons
RWB 6104 WMNX Page 3Table of ContentsGeneral Information Hazard Defi nitions ...
Page 4 RWB 6104 WMNX Hazard Defi nitions •General InformationGeneral InformationWithin the boundaries of the hazard warning, there will be information
RWB 6104 WMNX Page 5Figure 1. Burner label locationBoiler ModelBurner Spec Firing Rate (GPH)Air Tube Combina-tionInsertion Primary NozzleAlternate
Page 6 RWB 6104 WMNX General InformationTable 2. – Burner Specifi cationsCapacityLB & LCFiring rate: 0.40 – 1.35 GPH Input: 56,000 – 189,000
RWB 6104 WMNX Page 7Inspect/Prepare Installation SiteA chimney fl ue shall extend at least 3 feet above the highest point at which the chimney come
Page 8 RWB 6104 WMNX Connect Outside Air Duct to NX AdapterThe outside air adapter must be installed by strictly following the kit installation instr
RWB 6104 WMNX Page 9Verify that the air tube installed on the burner provides the correct insertion depth. See Figure 4.The end of the air tube sh