WM97+ gas-fired water boilerBoiler Manual
– 104 –
Figure 112 WM97+ control display toggles when in lockout, with screen flashing red to gray
Troubleshooting (continued)
WM97+ control fault indications
1. The WM97+ control provides diag-
nostic information for both automatic
reset conditions and manual reset
conditions. See Figure 84, page 74 for
information available on the WM97+
control display and navigation instruc-
tions for all menus.
2. Figure 112 shows the screen behavior
during an automatic or manual reset
condition. The table below the display
illustration lists manual reset condi-
tions and how to reset from them.
3. Figure 113, page 105 lists conditions
that will cause the control to display
a constant red screen. The boiler will
automatically restart if the condition
self-corrects or the technician uses the
WM97+ control’s manual reset screens
to reset.
Make sure to determine the causes of outages. Do not leave the boiler operating without a com-
plete diagnosis.