WM97+ gas-fired water boilerBoiler Manual
Venting & air — general (cont.)
Figure 18 Vent and air piping materials — Use only the materials listed below, ensuring that all materials meet
local codes (see Figure 123, page 119 for part/kit numbers)
Item Material
Standards for installations in:
United States Canada
(Note 2)
Plastic piping materials Vent or air piping Vent piping Air piping
Vent or air pipe
&
fittings
PVC schedule 40 ANSI/ASTM D1785 ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
PVC-DWV schedule 40 (Note 1) ANSI/ASTM D2665 NA
CPVC schedule 40 (Note 1) ANSI/ASTM F441 ULC S636
PVC & ABS pipe
cement & primer
PVC ANSI/ASTM D2564/F656 ULC S636
Use only cement
and primer
suitable for piping
material used
CPVC (Note 1) ANSI/ASTM F493 ULC S636
Polypropylene
vent pipe, fittings,
terminations and
cement
Simpson-Duravent — Obtain all materials from M&G
Simpson-Duravent
Centrotherm Eco Systems InnoFlue® Single-wall
Obtain all materials from Centrotherm
See manufacturer’s literature for
detailed information
MUST USE LOCKING
COLLAR ON EVERY JOINT
ULC S636
PVC, PVC-DWV,
CPVC or
polypropylene
AL29-4C stainless steel piping materials
Vent pipe
AL29-4C
stainless
steel
Heat Fab, Inc. — Saf-T-Vent
®
Z-Flex, Inc. — Z-Vent II
Dura-Vent — FasNSeal™
Metal-Fab, Inc. — CORR/GUARD
Centrotherm Eco Systems — InnoFlue®
Certified for Category IV and
direct vent appliance venting
Certified for Category IV and direct vent
appliance venting
Weil-McLain stainless steel bird screens, 2” or 3” (purchase separately) — see Figure 123, page 119 for part numbers
Note 1: Weil-McLain concentric vent kits are made from PVC
pipe and ttings.
Note 2: System 636 PVC concentric terminations utilize PVC
pipe/ttings certied to ULC S636.
If ULC S636 compliance is required, use only System
636 pipe, ttings and cement.
DO NOT mix piping from dierent pipe manufacturers
unless using adapters specically designed for the
purpose by the manufacturer.
Every joint on polypropylene vent piping must
include a locking collar.
DO NOT use cellular core pipe.
ADAPTERS — AL29-4C piping — Install a PVC-to-
stainless adapter supplied by the AL29-4C stainless
pipe manufacturer at the 3” PVC boiler vent connection
and at the termination (if using Weil-McLain plate or
concentric PVC termination).
ADAPTERS — Polypropylene piping — Provide adapt-
ers from polypropylene pipe to the 3” PVC connections
at the boiler and at terminations, if required (Weil-
McLain sidewall plate, for example).
ADAPTERS — If using 2” piping, where approved for
the application, provide adapters for the 3” PVC boiler
connections and at the terminations, if required (Weil-
McLain sidewall plate, for example)
ALL vent and air pipes require a BIRD SCREEN at each termination. Most kits do not include
the bird screens. Purchase bird screens separately from Weil-McLain or vent kit supplier if
not included. [Note — bird screening is integral to the 3” PVC Weil-McLain sidewall vent
cap, supplied standard with all WM97+ boilers. No additional screening is required.]
USE SWEEP ELBOWS FOR ALL VENT AND AIR PIPING — DO NOT use short
radius elbows for vent or air piping. Boiler performance could be aected.