Weil-McLain WM97+70 Specifications Page 77

  • Download
  • Add to my manuals
  • Print
  • Page
    / 136
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 76
Part number 550-142-120/0113
– 77 –
WM97+ gas-fired water boilerBoiler Manual
HEAT SETTINGS menus
System type Display Preset temperatures (see next page for description of settings)
MAX SUPPLY
Temp
MIN OUTDOOR
Temp
MIN SUPPLY
Temp
MAX OUTDOOR
Temp
Fan-coil FCL 190 0 140 70
Finned tube baseboard FTB 180 0 130 70
Cast iron baseboard CIB 180 0 120 70
Cast iron radiators CIR 180 0 120 70
Radiant – slab on grade RSG 120 0 80 70
Radiant – thin slab RTS 140 0 80 70
Radiant – below floor (staple up) RFU 160 0 90 70
Radiant – above floor (sleeper system) RAF 140 0 90 70
Custom CUS 190 0 70 70
Figure 87 HEAT SETTINGS menus (see Figure 89, page 79 for setting values and descriptions)
See table below
for system type
explanations
Speed settings — See
page 100 for blower speed
adjustment procedure and
acceptable speeds.
Page view 76
1 2 ... 72 73 74 75 76 77 78 79 80 81 82 ... 135 136

Comments to this Manuals

No comments